April 21, 2008

NetApp manages to keep its cool

Green 15 2008: Upgrading to a higher-density datacenter calls for a smart, energy-efficient cooling strategy

With its 7,000-square-foot datacenter nearing capacity, NetApp decided last year to squeeze more out of the space. By consolidating servers and replacing older hardware, the company created an energy-efficient, high-density facility with superior server utilization. That, in and of itself, is a worthy sustainable-tech project, but special kudos go to NetApp's unsung heroes who dealt with the upgraded datacenter's dirty little secret – a whole lot of hot air.

NetApp, a Silicon Valley-based maker of storage and data management products, originally built its datacenter in 2004. In order to prevent servers from overheating, the basic design had racks arranged in hot-and-cold aisles for collecting and expelling hot air, as well as air handlers equipped with economizers.

"Our design in 2004 was considered somewhat leading edge," says Ralph Renne, site operations manager at NetApp, adding that wiring, cabling, and air-conditioning systems were placed near the ceiling instead of under a raised floor, since cold air falls and hot air rises.

The air-conditioning units, though, operated at an inefficient 8-degree Fahrenheit Delta T (or the temperature difference between the supplied cool air and the returning hot air). The short 8-degree Delta T cycle meant that the overall room temperature needed to be kept at a cool 55 degrees in order to provide adequate removal of the heat in the room.

If the outside air was 55 degrees or below, economizers (which control the use of outside air) would kick in. If the outside air was slightly more than 55 degrees, then the economizers would blend this air with cool air generated from the air conditioners to achieve 55 degrees. If the outside air was 65 degrees or higher, then the cooling system would have to bypass outside air by circulating cool air inside the datacenter – the costliest and most energy-intense option.

A dense datacenter changes the cooling rules
Transforming the facility into a high-density datacenter threw the cooling setup for a loop. The remake consisted of consolidating 343 servers to 177 via virtualization and server retirement, and replacing 50 storage systems with 10 new ones. The footprint of the storage equipment, in particular, was reduced from nearly 25 racks to just over 5 racks. Fewer storage machines meant less demand for chilled water and electricity. Specifically, savings for this higher-density setup included 94 tons of chilled water and 494,208 kWh of electricity, or $60,000 in annual savings.

The problem was, a higher-density design pushes out more heat in tighter spaces, so NetApp needed to get better at cooling. The trick lay in segregating hot and cold air, rather than merely arranging cold and hot air aisles. The latter allows too much mixing of hot and cold air, and thus supplied cold air quickly becomes returning hot air without having done much cooling work.

Renne and his team placed wireless temperature sensors on 388 server racks to gain a better understanding of hot and cold air spaces in the new high-density layout. They used vinyl curtains to enclose hot aisles so that hot and cold air couldn't mix as freely. They installed a cogeneration system that captures heat waste and turns it into electricity to power chillers.

Close

On Twitter now

Green IT

Powered by Twitter

On Twitter now

White Paper

D2D Virtual Tape Library Replication Primer

This whitepaper explains the terminology and concepts behind Data Replication technologies and establishes some sizing rules through worked examples. Learn the new paradigm in disaster tolerance—protect data anywhere.

Download now »

White Paper

An Alternative to Virtualization for Datacenter Cost Savings

Server virtualization is a popular option for dealing with mounting datacenter costs. Another equally promising approach is the use of an Application Delivery Controller. Citrix NetScaler provides a low-cost way for organizations to reduce their server count and accrue cost savings from a reduction in space, cooling, power and personnel.

Download now »

White Paper

Why Your Firewall, VPN, and IEEE 802.11i Aren't Enough to Protect Your Network

The emergence of WLANs has created a new breed of security threats to enterprise networks.

Included in HP ProCurve WLAN solutions is security technology that alleviates threats from WLANs through:
* Monitoring wireless activity inside and out of the enterprise
* Classifying WLAN transmissions into harmful and harmless
* Preventing transmissions that pose a security threat to the enterprise network
* Locating participating devices for physical remediation

Download now »

White Paper

Bringing the Edge to the Data Center

Effectively address data protection challenges, implementing solutions that help store and protect business–critical data while cutting costs and improving efficiency and reliability.

Download now »

Sign up to receive InfoWorld Resource Alerts

Subscribe to the Today's Headlines: First Look Newsletter

Find out what will be news for the day, with our first-thing-in-the-morning briefing.

©1994-2009 Infoworld, Inc.